The only controller needed for all of your water quality measurements.
The Hach SC1000 Multi-parameter Universal Controller is a state-of-the-art modular transmitter system. The SC1000 consists of a Display Module and at least one Probe Module. Probe Modules for the SC1000 can be networked together to accommodate up to 32 digital sensors or analyzers. The SC1000 Display Module is intuitive, with an easy to use interface and large color touch-screen display that can be used for any number of parameters. One Display Module controls one or more Probe Modules connected by a digital network. The Display Module is fully portable, and can be disconnected and moved anywhere within the network. The Hach SC1000 Display Module is available with GSM/GPRS, Ethernet, and TCP/IP capability.
| Alarm | Low alarm point, low alarm point deadband, high alarm point, high alarm point deadband, off delay, and on delay |
| Analog Inputs | No Input Module |
| Analog Output | No Output Module |
| Analog Output Functional Mode | PID, high/low phasing, setpoint, deadband, overfeed timer, off delay, on delay |
| Certifications | European Certifications: CE per 73/23/EEC and 89/336/EEC TUV-GS to EN 61010-1 EN 61326 Amd’s 1 & 2 |
| Communication | Modbus® (RS485): Advanced communications/networking with PLC or SCADA system directly from analyzer Profibus® DP/V1 (certified) GSM/GPRS Quad-band cellular module (FCC and IC approved, EU and US only) Ethernet service port, RJ45, 10 MB/s |
| Communication Capabilities | Profibus DP |
| Conduit for Relay Connection | Yes |
| Dimensions (H x W x D) | 150 mm x 315 mm x 250 mm |
| Display | ¼ inch VGA graphical backlit TFT color Glas/Glas-Touch screen, high resistance 320 x 240 pixels |
| Display Viewing Area | 11.4 x 8.6 cm (4.5 x 3.4 in) |
| Enclosure Rating | IP65 |
| Inputs | Up to 12 analogue 0-20 mA, maximum impedance 500 Ohms per probe module. Additional inputs are available with additional probe modules. |
| Material Enclosures | ABS (display module) and metal (probe module) enclosure with corrosion resistant finish |
| Mounting | Surface, panel, and pipe (horizontal and vertical) with optional sun shield |
| Operating Temperature Range | -20 – 55 °C / 0 – 95% relative humidity, non-condensing |
| Output | Up to 12 analog 0/4-20 mA, maximum impedance 500 Ohms per probe module.
Additional analog outputs with additional probe modules. Optional digital communcations via Modbus® (RS485) and Profibus® DP/V1. |
| Power Options | 100-240V, no power cord, with conduit |
| Prognosys | No |
| Relays | No Relay |
| RTC Module | No |
| Sensors | 6 |
| Storage Conditions | -20 to 70 °C (-4 to 158 °F), 0 to 95% relative humidity, non-condensing |
| Warranty | 12 months |
| Weight | Approximately 6.5 kg (depending on configuration) |